[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not installed. Two equalizer outlets on the skimmers are not plugged.
Do not operate the pool when the outlet covers are not installed. PLUG THE 2 SKIMMER EQUALIZER LINES THAT ARE NOT PLUGGED. Correct By: 15-Jun-2021

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR THE FLOW METER. Correct By: 15-Jun-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST pH. Correct By: 15-Jun-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 14-June-2021


Comments
THE PROPOSED DRAIN COVERS FOR THE MAIN DRAINS HAVE A FLOW RATING THAT WILL NOT MEET THE FLOW REQUIREMENTS OF THE POOL. THE MINIMUM FLOW FOR THE POOL IS 408 GPM. THE MAIN DRAIN COVERS MUST HAVE A FLOW RATING OF AT LEAST 408 GPM.

The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions.

Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals.