3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. The flow switch is not connected.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH. Correct By: 30-Jun-2021
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 30-Jun-2021
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE DISINFECTION CHEMICAL FEEDER (the Stenner 45M5 was replaced with the Flex Flo A1N20A-4T Correct By: 30-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-June-2021
Comments |
---|
THE DEPTH MARKINGS MUST BE NO MORE THAN 25 FT APART. THE WADING POOL MUST HAVE AT LEAST 4 DEPTH MARKINGS AROUND THE POOL. SOME OF THE MARKINGS ARE FADING AND WILL NEED T BE REPAINTED BEFORE NEXT SEASON. The operator was observed performing onsite chemical tests appropriately . The Certificate of Compliance for the main drain cover is available in the equipment room. Our records show that the main drain suction outlet covers (AquaStar WAV12) were installed on 6-9-19. The covers has a 5 year life span and must be replaced before 6-9-24. |