3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow switch for ACC unit was not tested monthly and recorded.
Provide records indicating that the unit is being tested monthly. Correct By: 21-Jun-2023
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. Correct By: 21-Jun-2023
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. Correct By: 21-Jun-2023
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week. Correct By: 21-Jun-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 15-June-2023
Comments |
---|
Our records show that the main drain suction outlet covers (AquaStar P18) were installed 9/10/2018. The covers have a 5 year life span and must be replaced before 9/10/2023. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm Keep the equipment room locked when pool is open. |