[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 28-Jul-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE FLOW RATE TO AT LEAST 69 GPM Correct By: 26-May-2022
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. INSTALL A PRESSURE GAUGE AFTER THE PUMP SO THE FLOW RATE OF THE WATERFALL PUMP CAN BE DETERMINED. Correct By: 28-Jul-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 26-July-2021


Comments
PLEASE ADDRESS THE REPEAT VIOLATIONS (ORP AND PRESSURE GAUGE) IMMEDIATELY. REPLACE PUMP IF NECESSARY TO INCREASE FLOW RATE BEFORE NEXT YEAR.