[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 09-November-2022


Comments
POOL WAS NOT OPEN AT THE TIME OF INSPECTION.

CDC RECOMMEND CHLORINE LEVEL NOT TO EXCEED 10 PPM. REDUCE CHORINE LEVEL BEFORE REOPENING.

ADJUST THE pH AFTER REDUCING THE CHLORINE.

DO NOT USE THE "CHEMGUARD" CHEMICAL FEEDER IN THE POOL OR SKIMMER.

THE EMERGENCY PHONE IN THE POOL AREA MUST BE ANSWERED MORE QUICKLY. WHEN CHECKING THE PHONE IT RANG 8 TIMES BEFORE IT WAS ANSWERED.

WHEN HAND FEEDING THE POOL WITH CHEMICALS, RECORD THE TYPE AND AMOUNT ON THE LOG SHEETS.

TEST ALKALINITY WEEKLY.

RECORD ON THE LOG SHEETS WHEN THE POOL IS CLOSED.

DO NOT MIX AND MATCH THE TESTING REAGENTS. REAGENTS ARE SPECIFIC TO A COMPANY AND TEST VIAL.