[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. SUBMIT AN ERN TO ODH FOR THE REPLACEMENT OF THE DISINFECTION CHEMICAL FEEDER PUMP. STENNER 45M5 WAS REPLACED WITH A FLEXFLO A1N30A-7T.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE MISSING WEIRS IN THE SKIMMERS.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR/REPLACE FLOW METER.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 21-July-2022


Comments
LIFEGUARD MUST BE POSITIONED AT THE EDGE OF THE POOL SO THE BOTTOM OF THE BOTTOM CAN BE OBSERVED.

POST A COPY OF THE MAIN DRAIN COVER CERTIFICATE OF COMPLIANCE IN THE EQUIPMENT ROOM.