3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not secured. Two screws are missing in each main drain cover.
Do not operate the pool when the outlet covers are not secured. Secure the covers prior to the pool being placed back into operation.
INSTALL ALL 4 SCREWS IN THE MAIN DRAIN COVERS.
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 22-Jun-2023
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present. Hose bib connection in the equipment room is not back flow protected.
Remove all cross connection hazards from the pool area.
INSTALL A VACUUM BREAKER ON THE HOSE BIB IN THE EQUIPMENT ROOM.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR FLOW METER. Correct By: 21-Jun-2023
3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
The operating water level of the pool was not maintained.
Decrease the volume of the pool water until the pool operating water level is restored.
LOWER WATER LEVEL SO THAT THE SKIMMERS CAN FUNCTION PROPERLY Correct By: 21-Jun-2023
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 15-June-2023
Comments |
---|
Our records show that the main drain suction outlet covers (AquaStar WAV 12) were installed 8/1/2018. The covers have a 5 year life span and must be replaced before 8/1/2023. The cover has a flow rating of 274 gpm. When replacing the covers, ensure that the new covers' flow rating will not be exceeded. Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department. The operator was observed performing onsite chemical tests appropriately |