3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is .2, level than the required level.
This violation is a critical operational item and poses an imminent health hazard. THE POOL MUST CLOSE UNTIL THE VIOLATION IS CORRECTED. Correct By: 14-Jun-2018
3701-31-04 (B)(6)(j) / All SVRS devices are maintained/ functional and tested
Critical SVRS was not tested and recorded.
TEST AND RECORD THE FUNCTION OF THE SVRS MONTHLY. Correct By: 15-Jun-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER AT LEAST MONTHLY. Correct By: 15-Jun-2018
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The chlorine feeder was replaced with submitting an Equipment Replacement Notification to ODH.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE CHLORINE FEEDER. Correct By: 28-Jun-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
CONSULT WITH A PLUMBING INSPECTOR ON PROVIDING THE AN AIR GAP FOR THE FILTER BACK WASH DISCHARGE. Correct By: 28-Jun-2018
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
PLACE AN ADDITIONAL NO DIVING SIGN ON THE DECK BETWEEN THE GUARD CHAIR AND THE LADDER ON THE HIGHWAY SIDE OF THE POOL. Correct By: 28-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-June-2018
Comments |
---|
WATER LEVEL IS A LITTLE HIGH FOR EFFECTIVE SKIMMING. THE FLOW METER IS HARD TO READ. THE FLOW RATE MUST NOT EXCEED THE MAX FLOW RATING OF THE DRAIN COVERS. |