[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The flow rate is 44 gpm. The max filter flow is 38 gpm.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO BETWEEN 38 GPM AND 32 GPM. Correct By: 17-Jul-2017
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. pH is 7.0
Treat the pool water so that the pH is within the acceptable range. ADJUST pH TO BETWEEN 7.2 AND 7.8. Correct By: 15-Jul-2017


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 14-July-2017


Comments
PLACE THE MAX (38 GPM) AND MIN (32 GPM) FLOW RATE BY THE FLOW METER.

THE DRAIN COVER APPEARS TO BE NEW WATER SOLUTIONS DS360 WHICH HAS A LIFE SCAN OF 3 YEARS. REPLACE THE COVERS IF THEY ARE MORE THAN 3 YEARS OLD. COMPLETE THE CERTIFICATE OF INSTALLATION AND KEEP IT ALONG WITH THE CERTIFICATE OF COMPLIANCE AND THE INSTALLATION INSTRUCTIONS.