3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The main drain covers have exceeded their life span.
REPLACE THE MAIN DRAIN COVERS AND RETAIN THE CERTIFICATE OF COMPLIANCE, THE INSTALLATION DATE AND THE NAME OF INSTALLER. Correct By: 09-Jul-2019
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is below 1 ppm.
This violation is an imminent health hazard.
CLOSE THE POOL UNTIL THIS VIOLATION IS CORRECTED AND THE HEALTH DEPARTMENT IS NOTIFIED OF CORRECTION. Correct By: 02-Jul-2019
3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The pool does not has water circulation.
This is critical violation and poses an imminent health hazard.
CLOSE THE POOL UNTIL THE CIRCULATION CAN BE REPAIRED. Correct By: 02-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-July-2019
Comments |
---|
Our records show: The main drain suction outlet cover (AquaStar WAV 12) was installed 5/1/2014. The cover has a 5 year life span and must be replaced before 5/1/2019. |