3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not compliant covers.
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation.
PLUG THE SKIMMER EQUALIZER LINES UNDER THE SKIMMER BASKET. Correct By: 25-Jun-2021
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored improperly. Chlorine stored on top of cyanuric acid..
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
MOVE THE CHLORINE FROM ON TOP OF STABILIZER (CYANURIC ACID). DO NOT STORE DIFFERENT CHEMICALS ON TOP OF EACH OTHER. Correct By: 24-Jun-2021
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected.
THE CHLORINE CHEMICAL FEEDER MUST BE USED. HAND FEEDING CHLORINE IS NOT ACCEPTABLE ON AN ONGOING BASIS. Correct By: 26-Jun-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The weirs in the skimmers are missing.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE MISSING WEIRS IN THE SKIMMERS. Correct By: 25-Jun-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The wrong size skimmer basket is in one skimmer.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE SMALL SKIMMER BASKET WITH THE PROPER SIZE BASKET. Correct By: 23-Jul-2021
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. Handrail loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN HANDRAIL Correct By: 25-Jun-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable. The new door from the rest-rooms is not latchable.
Repair gates or doors in order to be self-closing and lockable. THE DOOR FROM THE BATHROOMS MUST BE SELF-LATCHING AND HAVE THE ACTUATING DEVISE AT LEAST 38 INCHES ABOVE THE GROUND. Correct By: 23-Jul-2021
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
Corrected During Inspection 12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
KEEP THE RING BUOY VISIBLE FROM THE DECK. Correct By: 23-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 23-June-2021
Comments |
---|
The operator was observed performing onsite chemical tests appropriately The Certificate of Compliance for the main drain cover is available in the equipment room. The main drain suction outlet cover (Waterway 640-472xV) was installed on 6-1-19. The cover has a 7 year life span and must be replaced before 6-1-26. |