3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical Disinfection system was not operating properly at the time of the inspection
Do not operate the pool when disinfection system is not operating properly. Ensure that the disinfection system is functioning properly prior to placing the pool back into operation.
DO NOT OPEN THE WADING POOL UNTIL THE DISINFECTION CHEMICAL PUMP IS REPAIRED. WADING POOL WAS NOT OPEN AT THE TIME OF INSPECTION. POOL CLOSED SIGN WAS NOT THE GATE. Correct By: 10-Jun-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 10-Jun-2022
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 50 GPM
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 10-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 10-June-2022
Comments |
---|
WADING POOL WAS NOT OPEN AT THE TIME OF INSPECTION. The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (Aqua Star A10RDFR) were installed 5/12/21. The covers have a 5 year life span and must be replaced before 5/12/2026. |