[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool. SUBMIT AN ERN TO ODH FOR THE REPLACEMENT OF THE DISINFECTION FEEDER. Correct By: 04-Jun-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIR IN THE SKIMMER. Correct By: 04-Jun-2021
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. The jet pump does not have a means of determining the flow rate.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. INSTALL A VACUUM AND PRESSURE GAUGE FOR THE SPA JET PUMP. POST THE PUMP CURVE AND THE CALCULATION FOR DETERMINING THE FLOW RATE. Correct By: 04-Jun-2021
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. No depth markings are on the deck.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. INSTALL AT LEAST 2 DEPTH MARKINGS ON THE DECK WITHIN 2 FEET OF THE WATERS EDGE AT LEAST 4 INCHES IN SIZE. Correct By: 04-Jun-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. ADJUST THE pH
Treat the pool water so that the pH is within the acceptable range. Correct By: 04-Jun-2021


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 02-June-2021


Comments
The Certificate of Compliance is not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. Our records show that the main drain suction outlet covers (AquaStar WAV 12) were installed 5/26/2018. The covers have a 5 year life span and must be replaced before 5/26/2023.