[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free Chlorine level was below the required level of 1 ppm
This violation is a critical operational item and poses an imminent health hazard. DO NOT OPERATE THE SPRAY GROUNDS UNTIL THE LEVEL OF FREE CHLORINE IS 1 PPM OR HIGHER. Correct By: 27-Jul-2018

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 30-Jul-2018
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 30-Jul-2018


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 27-July-2018