3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not secured. Covers must screws.
Do not operate the pool when the outlet covers are not secured. Secure the covers prior to the pool being placed back into operation.
INSTALL ALL 4 SCREWS IN MAIN DRAIN COVER AS DIRECTED BY MANUFACTURER'S INSTRUCTION.
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Repeat Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
TEST AND RECORD CYA WEEKLY.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Acid feeder nor connected.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR ACID FEEDER.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and lockable. Gate does not self-latch.
Repair gates or doors in order to be self-closing and lockable.
REPAIR GATE SO THAT IT SELF-LATCHES.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 03-August-2022
Comments |
---|
CDC RECOMMENDS LOWERING CHLORINE LEVEL TO 10 PPM OR BELOW. |