3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents. Liquid chemicals are stored over dry chemicals in the filter room.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
ORGANIZE THE CHEMICALS THAT ARE STORED IN THE FILTER ROOM. MOVE LIQUID CHEMICALS FROM OVER DRY CHEMICALS. Correct By: 23-Jan-2018
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. The water testing was not done daily. The ACC was not tested and recorded monthly.
All facility records must be maintained and available for review upon request.
SCHEDULE FOR SOMEONE TO TEST THE WATER EVERY DAY. ALSO, TEST AND RECORD THE FUNCTION OF THE ACC FLOW SWITCH. Correct By: 30-Jan-2018
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. The handrail is loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE HANDRAIL. Correct By: 30-Jan-2018
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided with enough supplies to stop bleeding.
Provide first aid equipment, including a first aid kit, at the pool at all times.
PROVIDE LARGER GAUZE PADS OR OTHER SUPPLIES TO THE FIRST AID KIT TO STOP BLEEDING. Correct By: 30-Jan-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 23-January-2018
Comments |
---|
"WATER TESTING AND RECORD KEEPING", "CRITICAL OPERATIONAL ITEMS", AND CDC FECAL ACCIDENT RESPONSE HANDOUTS WERE SUPPLIED TO THE OPERATOR AND REVIEWED TO ENSURE THAT THE OPERATOR IS KNOWLEDGEABLE OF THE REQUIRED CHEMISTRY LEVELS, CRITICAL ITEMS WHERE THE POOL MUST CLOSE, AND HOW TO RESPOND TO A FECAL ACCIDENT. THE OPERATOR SEEMED AWARE OF THESE ITEMS. |