[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The main drain covers are missing screws.
INSTALL ALL 4 SCREWS IN THE MAIN DRAIN COVERS. Correct By: 10-Aug-2020
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level was below 1 ppm.
This violation is a critical operation item and poses an imminent health hazard. CLOSE THE POOL UNTIL THE FREE CHLORINE LEVEL IS 1 PPM OR MORE. CALL THE HEALTH DEPARTMENT 440-219-7158 WHEN CORRECTED. Correct By: 03-Aug-2020

3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records. Records were for only every other day.
All facility records must be maintained and available for review upon request. RECORD THE WATER CHEMISTRY EVERY DAY THAT THE POOL IS OPEN, EVERY 4 HOURS. Correct By: 04-Aug-2020
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The reagents in the test kit were expired.
REPLACE THE REAGENT WITH FRESH ONES. Correct By: 10-Aug-2020


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 03-August-2020