[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week. RECORD CYA ON WEEKLY LOG SHEETS. Correct By: 08-Jun-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The weirs in the skimmers are sticking.
All equipment must be maintained in accordance with the manufacturers specifications. ADJUST/RIG THE SKIMMERS SO THAT THEY FLOAT FREELY WITH THE WATER. Correct By: 08-Jun-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 01-June-2021


Comments
KEEP AN EYE ON THE FLOW RATE.

When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm

The Certificate of Compliance for the main drain cover is available in the equipment room. Our records show that the main drain suction outlet covers (Hayward WG1048E) were installed 10/1/2017. The covers have a 7 year life span and must be replaced before 10/1/2024.