3701-31-04 (B)(1)(k) / Chemical storage or use shall not result in imminent health hazard.
Critical Different tyes of liquid chemicals were stored on top of each other in the filter room.
STORE DIFFERENT CHEMICALS SEPARTELY AND NOT ON TOP OF EACH OTHER Correct By: 08-Nov-2018
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(3) / Staff is trained and knowledgeable
Repeat Staff was not trained or knowledgeable in pool operations. Staff that was taking care of the pool is not working there now.
Train staff in pool operations, operation of equipment, chemical storage, use and handling and appropriate emergency procedures.
PROVIDE STAFF TO TAKE CARE OF THE POOL. THE POOL SHOULD NOT REMAIN OPEN UNTIL STAFF IS AVAILABLE TO MAINTAIN AND CHECK THE POOL. Correct By: 06-Nov-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 05-Nov-2018
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat Emergency device (telephone) did not have emergency numbers posted by it.
Ensure that the emergency device has emergency phone number posted by it. Correct By: 10-Nov-2018
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 08-November-2018