3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The equalizer lines from the skimmers were not covered with approved covers.
Screws were missing in the drain covers.
PLUG THE SKIMMER EQUALIZER LINES AT THE POOL WALL OR COVER OPENING WITH AN VGB APPROVED COVER.
INSTALL ALL 4 SCREWS IN THE DRAIN COVERS. Correct By: 11-Aug-2020
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Corrected During Inspection The equipment room was not locked.
KEEP THE EQUIPMENT ROOM LOCKED. Correct By: 05-Aug-2020
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
KEEP BAG OF SODIUM BICARB OFF OF THE FLOOR. Correct By: 05-Aug-2020
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIRS IN THE SKIMMERS. Correct By: 11-Aug-2020
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER. Correct By: 11-Aug-2020
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The gate was open at the time of inspection.
The gate did not self-close.
KEEP THE GATE CLOSED.
REPAIR THE GATE SO THAT IT SELF-CLOSES. Correct By: 11-Aug-2020
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Reagent R-0003 was not available for testing total chlorine (and combine chlorine)
PROVIDE REAGENT R-0003. RE-TEACH GUARD HOW TO TEST CHLORINE AND pH. Correct By: 11-Aug-2020
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
Obtain fresh reagents and store them properly.
STORE REAGENTS OUT OF THE SUN. Correct By: 05-Aug-2020
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
Corrected During Inspection A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
Provide a proper floatation device at all times.
KEEP RING BUOY ON THE DECK DURING POOL OPERATION. Correct By: 05-Aug-2020
3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
Corrected During Inspection A back/spine board without a head immobilizer and straps was not provided at the unguarded pool.
Provide the back/spine board at the pool at all times.
KEEP THE SPINE BOARD ON THE DECK DURING POOL OPERATION. Correct By: 05-Aug-2020
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
REPAIR THE EMERGENCY PHONE. Correct By: 11-Aug-2020
3701-31-04 (E)(3)(d) / "WARNING or DANGER - POOL CLOSED" sign(s) posted-when the pool is closed
The pool "WARNING or DANGER - POOL CLOSED" sign was not available.
PROVIDE A "WARNING or DANGER - POOL CLOSED" sign at all times the pool is not available for use. Correct By: 11-Aug-2020
3701-31-04 (E)(4)(c)(i) / Lifeguards have direct line of sight of all useable areas of the pool surface and bottom
Corrected During Inspection Lifeguards did not have direct line of sight of all useable areas of the pool surface and bottom. Guard was positioned at the table away from the edge of the pool.
Provide more lifeguards so that all areas of the pool surface and bottom can be within a lifeguards direct line of sight.
POSITION LIFEGUARD AT THE EDGE OF THE POOL SO THEY CAN SEE THE BOTTOM. Correct By: 05-Aug-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 04-August-2020
Comments |
---|
The main drain suction outlet cover (New Water Solutions DS 360) was installed on 6-29-16. The cover has a 5 year life span and must be replaced before 6-29-21. The cover has a flow rating of 246 gpm. The Certificate of Compliance was not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm |