[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical One of the main drains is missing a screw.
REPLACE THE MISSING SCREW IN THE MAIN DRAIN. Correct By: 14-Jul-2020
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection The free chlorine level was 0 ppm.
THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. THE VIOLATION WAS CORRECTED AT THE TIME OF INSPECTION. THE FREE CHLORINE LEVEL WAS 5.2 PPM AFTER 15 MINUTES. KEEP A CLOSE EYE ON THE CHLORINE LEVELS. Correct By: 08-Jul-2020

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIRS IN THE SKIMMERS. Correct By: 14-Jul-2020
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 50 GPM IS THE MINIMUM REQUIRED FLOW RATE WHEN THE VOLUME OF THE POOL IS 5984 GALLONS. Correct By: 26-May-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat A perimeter fence must be around the wading pool.
PLACE FENCE AROUND THE WADING POOL. SUBMIT PLACES TO THE OHIO DEPARTMENT OF HEALTH FOR APPROVAL. Correct By: 26-Aug-2020
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Emergency phone numbers must be posted by the phone
POST "DIAL 911 IN CASE OF EMERGENCY" BY THE EMERGENCY PHONE" Correct By: 14-Jul-2020


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 07-July-2020


Comments
-The Certificate of Compliance was not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review.

-Our records show that the main drain suction outlet cover (Paramont SDX 159-2212) was installed 5/1/2016. The cover has a 5 year life span and must be replaced before 5/1/2021. Let me know if this information is not correct.

THE VOLUME OF THE POOL WAS RECALCULATED AT 5984 GALLONS WHEN THE WATER DEPTH IS 8 INCHES AROUND THE PERIMETER AND 18 INCHES AT THE CENTER. THIS IS WHEN THE WATER IS AT THE LEVEL OF THE CENTER OF THE SKIMMER OPENING.