3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Repeat Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas.
LOCK WOMEN'S SPA EQUIPMENT ROOM DOOR.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FLOW SWITCH FUNCTION ON THE LOG SHEET MONTHLY.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat f
T
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 29-February-2024
Comments |
---|
REPLACE THE DRAIN COVERS. KEEP THE CERTIFICATE OF COMPLIANCE IN THE OFFICE. The Certificate of Compliance for the main drain covers is available in the equipment room. Our records show that the main drain suction outlet covers (AquaStar WAV12) were installed 3/26/2019. The covers have a 5 year life span and must be replaced before 3/26/2024. |