3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Information on the date of installation of the main drain covers was not available.
IF THE DATE OF INSTALLATION OF THE MAIN DRAIN COVERS IS UNKNOWN OR IF THE DRAIN COVERS HAVE BEEN IN PLACE FOR 7 YEARS OR MORE THEY MUST BE REPLACED. RETAIN THE CERTIFICATE OF INSTALLATION AND THE INSTALLATION INSTRUCTIONS.
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The skimmer equalizer line outlets are not covered with VGB approved covers.
INSTALL VGB APPROVED COVERS OVER THE SKIMMER EQUALIZER LINE OUTLETS OR PLUG THE EQUALIZER LINES AT THE POOL WALL.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
LABEL THE CHLORINE TANK. Correct By: 25-Jun-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
SHORTEN THE FILTER BACKWASH LINE AT LEAST 2 INCHES TO PROVIDE AN AIR GAP. Correct By: 25-Jun-2018
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
The flow meter is improperly located. It is 25 inches from Turbulence.
Properly install a flow meter.
THE FLOW METER MUST BE 10 TIMES THE DIAMETER OF THE PIPE DOWNSTREAM FROM TURBULENCE AND 5 TIME THE DIAMETER OF THE PIPE UPSTREAM FROM TURBULENCE.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE HANDRAILS. Correct By: 25-Jun-2018
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
PLACE THE FIRST AID KIT IN A LOCATION THE SWIMMERS CAN USE IT. Correct By: 25-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-June-2018
Comments |
---|
I WAS NOT ABLE TO DETERMINE IF THE EMERGENCY PHONE OPERATES PROPERLY. PLEASE CHECK |