3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not installed.
Do not operate the pool when the outlet covers are not installed.
PLUG THE SKIMMER EQUALIZER OUTLETS OR COVER WITH AN APPROVED COVER.
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN FOR THE REPLACEMENT OF THE DISINFECTION FEEDER.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FILTER PRESSURE GAUGES.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and latchable.
Repair gates or doors in order to be self-closing and latchable.
THE GATE MUST LATCH SO IT WILL NOT OPEN WITH A PUSH.
Correct By: 24-Aug-2023
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
A FIRST AID KIT MUST BE AVAILABLE EVEN WHEN THE LIFEGUARD IS NOT PRESENT. Correct By: 24-Aug-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 22-August-2023
Comments |
---|
DO NOT BURN THE BUILDING DOWN BY REUSING A CHLORINE BUCKET FOR ACID TANK. |