[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request. TEST AND RECORD REQUIRED POOL READINGS TWICE A DAY. Correct By: 20-Nov-2020
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE THE FLOW RATE TO AT LEAST 27 GPM Correct By: 20-Nov-2020
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST THE pH Correct By: 16-Nov-2020


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 13-November-2020


Comments
THE AUTOMATIC CHEMICAL CONTROLLER (ACC) WAS READING THE pH AT 7.4, BUT THE pH IN THE POOL WAS 7.0. CALIBRATE THE ACC TO THE MANUAL TEST RESULTS.