3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The main drain cover screws are not fully seeded down completely.
COMPLETELY SCREW IN THE SCREWS ON THE DRAIN COVERS TO MAKE THE COVER SECURE. Correct By: 29-Jul-2020
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Free chlorine level is 0 ppm.
This violation is a critical operational item and poses an imminent health hazard. THE WADING POOL MUST CLOSE UNTIL THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM.. Correct By: 30-Jul-2020
3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The disinfection feeder is not operating properly.
REPAIR THE DISINFECTION FEEDER AND DISCONTINUE THE PRACTICE OF PUTTING CHLORINE PUCKS IN THE LIT BASKET ON THE PUMP. Correct By: 29-Jul-2020
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE PUMP. THE PUMP WAS REPLACED BETWEEN 2018 AND 2019 WITHOUT APPROVAL. Correct By: 29-Jul-2020
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE TO BETWEEN 14 AND 26 GPM. Correct By: 29-Jul-2020
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST THE ALKALINITY. Correct By: 31-Jul-2020
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 30-July-2020