[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 09-October-2020


Comments
The sanitarian attempted to make an inspection, but the pool was not open.
The operator indicated that the pool will remain closed for the near future.

BEFORE REOPENING
-MAKE AND RECORD REQUIRED TESTS, DAILY, WEEKLY, AND MONTHLY AS APPROPRIATE.
-REPLACE MISSING WEIRS IN THE SKIMMERS.
-REPLACE THE RUBBER COUPLING ON THE PIPE WITH RIGID PVC PIPE IN THE EQUIPMENT ROOM.
-REPLACE THE DRAIN COVERS AND KEEP THE CERTIFICATE OF COMPLIANCE WITH THE DATE OF INSTALLATION.
-PLACE A BACKFLOW PREVENTER (ASSE 1011) ON THE HOSE BIB IN THE EQUIPMENT ROOM.