[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. RESUBMIT THE EQUIPMENT REPLACEMENT FORM FOR THE DISINFECTION CHEMICAL FEEDER PUMP. Correct By: 29-Jun-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST pH. Correct By: 24-Jun-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 22-June-2023


Comments
Our records show that the main drain suction outlet covers (Lawson MLD-FGD-1212) were installed date on 5/1/2018. The covers have a 10 year life span and must be replaced before date 5-1-28.

Keep a copy of the certificate of compliance for the main drains for the wading pool.

The disinfection chemical feeder pump Blue White FlexFlo A1N20A-4T was replaced with a Blue White FlexFlo A1N20A-7T.