3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Free Chlorine is .2 which is less than the require level of 1 ppm.
This violation is a critical operational item and poses an imminent health hazard.
CLOSE THE POOL UNTIL THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM. Correct By: 15-Aug-2018
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. Correct By: 17-Aug-2018
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
KEEP THE PUMP ROOM LOCKED. Correct By: 17-Aug-2018
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemical containers were not stored properly.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
REMOVE THE BAG OF SODA ASH FROM THE FLOOR OF THE PUMP ROOM. Correct By: 17-Aug-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FUNCTION MONTHLY. Correct By: 17-Aug-2018
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 17-Aug-2018
3701-31-04 (B)(4)(a)(ix) / Chemicals added to the pool other than those used for disinfection
Repeat A record of chemicals added is not kept.
KEEP A RECORD OF THE CHEMICALS ADDED TO THE POOL OTHER THAN ROUTINE CHEMICALS FED THROUGH THE CHEMICALS FEEDERS. Correct By: 17-Aug-2018
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE WATER LEAKS AND MAINTAIN THE PROPER WATER LEVEL SO THE SKIMMERS WORK PROPERLY. Correct By: 15-May-2019
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPAINT THE 3 "ZERO DEPTH" MARKINGS AT THE END OF THE END. LETTERING MUST BE AT LEAST 4 INCHES IN HEIGHT AND NO MORE THAN 24 INCHES AWAY FROM THE WATER SURFACE. Correct By: 17-Aug-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The entry gate was left open.
KEEP THE ENTRY GATE CLOSED. Correct By: 15-Aug-2018
Facility Type: Special Use
[?] Inspection Type: Follow-up
Inspection Date: 31-August-2018