3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm.
-Observed free chlorine below 1ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
-Post pool as closed due to maintenance and repair defective equipment.
-Call HD when repairs are completed.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
-Observed a deficency in record keeping.
All facility records must be maintained and available for review upon request.
-Records of pool testing is required to be accomplished daily when pool is open.
-If pool is closed, an annotation (POOL CLOSED) is required to be noted in the day or days that the pool is closed.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 11-August-2022
Comments |
---|
A new chlorinator was installed. Pool is currently not receiving the correct amount of chlorine. The free chlorine test at .06ppm. Will require another re-inspection and remain closed until pool free chlorine is minimum 1ppm. |