3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATION ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE POOL UNTIL CORRECTED. CALL ME WHEN CORRECTED 440-219-7158. CLOSE WAS CLOSED AT THE TIME OF INSPECTION. Correct By: 08-Apr-2022
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 07-Apr-2022
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH). Pump replaced
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE CIRCULATION PUMP. Correct By: 11-Apr-2022
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results/ records were not maintained.
The test results/ records for these acc must be kept on site for review.
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH/PUMP INTERLOCK MONTHLY.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. Ladder missing tread on step.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
REPLACE MISSING TREAD ON THE TOP RUNG OF THE LADDER. Correct By: 18-Apr-2022
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
REPAIR OR REPLACE EMERGENCY PHONE IN POOL AREA. Correct By: 18-Apr-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-April-2022