[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The skimmer equalizer lines are not VGB compliant.
PLACE A VGB COMPLIANT COVER OVER THE SKIMMER EQUALIZER LINES OR PLUG THE EQUALIZER LINES AT THE POOL WALL. Correct By: 15-May-2019

3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Repeat Backflow prevention devices was not tested since 2014 per tag
Have the backflow prevention device evaluated or replaced so that backflow is prevented. HAVE THE BACKFLOW PREVENTER INSPECTED ANNUALLY. Correct By: 01-Aug-2018
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. THE FLOW RATE MUST BE INCREASED TO AT LEAST 372 GPM, BUT LESS THAN 564 GPM. Correct By: 25-Aug-2018
3701-31-04 (E)(3)(d) / "WARNING or DANGER - POOL CLOSED" sign(s) posted-when the pool is closed
The pool was closed but the "WARNING or DANGER - POOL CLOSED" sign(s) were not posted.
Post the "WARNING or DANGER - POOL CLOSED" sign at all times the pool is not available for use. Correct By: 01-Aug-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 24-July-2018


Comments
Corrections that have been made since the last inspection
-new drain covers have been purchased and waiting until the end of the season to install
-the skimmer weirs are in place and freely move
-the filter room is locked
-chemicals were not placed in the skimmers
-the spine board is out on the deck and available
-a sign indicating the location of the emergency phone is posted.
-reportedly, a ERN has been send to ODH for the replacement of the pump