3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical bag was store on the floor..
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
STORE BAG OF CHEMICAL OFF OF THE FLOOR. Correct By: 20-Sep-2023
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required flow meter was not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR FLOW METER. Correct By: 20-Sep-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH AFTER REDUCING THE CHLORINE LEVEL. Correct By: 20-Sep-2023
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST THE ALKALINITY AFTER REDUCING THE CHLORINE LEVEL. Correct By: 20-Sep-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-September-2023
Comments |
---|
CDC DOES NOT RECOMMEND CHLORINE LEVELS HIGHER THAN 10 ppm. |