[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The skimmer equalizer outlets are not covered with a VGB compliant cover.
INSTALL A VGB COMPLIANT COVER OVER THE SKIMMER EQUALIZER OUTLET OR PLUG THE OUTLET AT THE POOL WALL. Correct By: 17-Jun-2019

3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. TIGHTEN THE HANDRAIL ON THE STEPS. Correct By: 17-Jun-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. ADJUST THE ALKALINITY Correct By: 17-Jun-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 13-June-2019


Comments
Our records show: The main drain suction outlet cover (AquaStar 12MF) was installed 5/1/2017. The cover has a 5 year life span and must be replaced before 5/1/2022.

-discard moldy or water damaged bandages in the first aid kit
-additional bottom stringer is needed on the bottom of the fence (closest to the playground equipment)
-it is not good practice to use a chemical bucket (5 gal) of one chemical to use as a storage tank for another chemical (muriatic acid). A supplier tank should be used.