3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
LABEL CHLORINE TANK Correct By: 13-Jul-2021
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR FLOW METER. Correct By: 13-Jul-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 13-Jul-2021
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 13-Jul-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 12-July-2021
Comments |
---|
MAIN DRAIN COVERS SHOULD HAVE A MINIMUM FLOW RATING AT LEAST THE MIN REQUIRED FLOW FR THE POOL (408 GPM) |