3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 331 GPM.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 02-May-2022
Comments |
---|
The Certificate of Compliance for the main drain covers are available in the equipment room. Our records show that the main drain suction outlet covers (Lawson MLD-FGD-1818) were installed 3/13/2020. The covers have a 10 year life span and must be replaced before 3/13/2030. Maximum flow rating is 816 gpm |