[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Throttle valve was not properly labeled.
LABEL THE THROTTLE VALVE OR BY THE FLOW METER WITH THE MAX AND MIN FLOWS. MAX IS 300 GPM, THE MIN IS 251 GPM. Correct By: 04-Jun-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The gate located furthest from the filter room does not self-close.
ADJUST THE GATE THAT IS FURTHEST FROM THE FILTER ROOM SO IT SELF-CLOSES AND THERE IS NOT A GAP BETWEEN THE GATE AND FENCE MORE THAN 6 INCHES. Correct By: 04-Jun-2018
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The alkalinity test reagents have expired.
REPLACE THE ALKALINITY REAGENTS WITH FRESH ONES. Correct By: 04-Jun-2018
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. REPAIR THE EMERGENCY PHONE. POST "EMERGENCY PHONE" ON THE CABINET THAT IT IS IN. Correct By: 04-Jun-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 31-May-2018


Comments
The drain cover was replaced on 4-19-18 with a Aquastar model 914101.

IT IS RECOMMENDED THAT HOT WATER BE SUPPLIED TO THE HAND SINK THAT IS OUTSIDE THE BATHROOMS.

WHEN THE POOL IS CLOSED POST A SIGN ON THE GATE THAT STATES "WARNING: POOL CLOSED".