3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
PLACE A LABEL ON THE CHLORINE TANK. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Backflow prevention devices were not inspected.
Have the backflow prevention device evaluated.
HAVE THE ASSE 1013 BACK FLOW PREVENTER INSPECTED ANNUALLY. DOCUMENT INSPECTION WITH A TAG OR OTHER MEANS. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP BETWEEN THE BOTTOM OF THE DRAIN FROM THE FILTER BACK WASH AND THE TOP OF THE SEWER STAND PIPE. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
A 7 inch gap exits between the bottom of the fence and the top of the ground under the white fence.
ADJUST OR REPAIR THE WHITE FENCE TO REDUCE THE GAP BETWEEN THE BOTTOM OF THE FENCE AND THE TOP OF THE GROUND TO LESS THAN 4 INCHES. Correct By: 30-Jun-2018
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook was not provided at the guarded pool.
Provide the non-telescopic reach pole at the pool at all times.
THE POLE MUST BE 12 FT LONG AND NON-ADJUSTABLE WITH A SHEPHERD'S CROOK. Correct By: 30-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 21-June-2018
Comments |
---|
RECOMMEND GFI OUTLETS IN THE FILTER ROOM. |