[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow rate is more than allowable by the filter and drain covers.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO LESS THAN 515 GPM BUT MORE THAN 343 GPM. Correct By: 05-Aug-2017
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Repeat Backflow prevention devices were not maintained to function properly. There area hose bibs without backflow protection.
Have the backflow prevention device evaluated or replaced so that backflow is prevented. INSTALL ASSE 10111 BACKFLOW PREVENTERS ON THE HOSE BIB BY THE WADING POOL FILTER AND ON THE HOSE BIB ON THE OUTSIDE OF THE FILTER ROOM INSIDE THE WADING POOL AREA. Correct By: 01-Apr-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 04-August-2017


Comments
PLEASE PLACE THE RING BUOY WITH 30-60 ROPE AND RESEARCH POLE WITH SHEPHERDS CROOK SO IT IS VISIBLE AND READY TO USE FROM DECK.