3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Bromine disinfectant residual was less than 2 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the bromine disinfectant residual is at 2 ppm or above prior to placing the pool back into operation.
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Skimmer weirs are missing.
Replace missing skimmer weirs.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Perimeter barrier gate needs to be self-closing and self-latching to prevent unauthorized entry.
Repair the perimeter barrier gate so that it is self-closing and self-latching.
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-June-2017