[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The certificate of compliance is not available for the drain covers.
OBTAIN THE CERTIFICATE OF COMPLIANCE AND THE INSTALLATION INSTRUCTION AND RETAIN FOR THE DRAIN COVERS. THE DRAIN COVERS APPEAR TO BE WATER SOLUTION DS 360. PLEASE VERIFY. Correct By: 06-Jul-2017

3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid, total chlorine and combine chlorine are not being tested and recorded at the proper frequency.
TEST AND RECORD THE CYANURIC ACID WEEKLY AND THE COMBINE, FREE AND TOTAL CHLORINE EVERY 4 HOURS AND THE TEMPERATURE DAILY. Correct By: 06-Jun-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The skimmers are missing the wirers (flappers).
REPEAT VIOLATION. All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE WEIRS OR INSTALL EQUIVALENT. Correct By: 06-Jul-2017
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Throttle valve was not properly maintained/adjusted. The throttle valve is not tagged.
Throttle valves must be maintained in the same position was when originally installed and approved. Restore the setting of the throttle valve and lock it into place. TAG THE THROTTLE VALVE OR THE PIPE BY THE FLOW METER WITH THE MAXIMUM ALLOWABLE FLOW ( ) AND MINIMUM REQUIRED FLOW 106 GPM. Correct By: 06-Jul-2017
3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
The operating water level of the pool was not maintained. Water level is at the top of the skimmers which is too high.
Increase the volume of the pool water until the pool operating water level is restored. REDUCE THE WATER LEVEL TO THE MIDDLE OF THE SKIMMER. Correct By: 09-Jun-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. The depth markings and "No diving" markings are faded and more than 25 ft apart.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. REPAINT THE DEPTH AND "NO DIVING" MARKINGS ON THE DECK NO MORE THAN 25 FT APART. Correct By: 06-Jul-2017
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The fence gate does not self-close.
REPEAT VIOLATION. INSTALL A SELF CLOSING GATE. Correct By: 06-Jul-2017
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The reagents in the pool test kit are expired.
REPLACE THE POOL TEST KIT. PLACE BEFORE THEY EXPIRE IN THE FUTURE. Correct By: 06-Jul-2017
3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
A spine board was not available for use at the time of the inspection.
PLACE THE SPINE BOARD OUT WHERE IT IS VISIBLE AND AVAILABLE FOR USE WHEN THE POOL IS OPEN. Correct By: 06-Jun-2017


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-June-2017