3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not tested monthly.
Provide records indicating that the ACC flow switch is being tested monthly.
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER LOW SWITCH MONTHLY. Correct By: 13-Jun-2019
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 13-Jun-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 13-Jun-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-June-2019
Comments |
---|
Our records show: The main drain suction outlet cover (Lawson MLD-FGD-1212) was installed date on 5/1/2010. The cover has a 10 year life span and must be replaced before 5/1/2020. |