[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER (ACC) FLOW SWITCH FUNCTION MONTHLY. REPAIR THE ACC FLOW SWITCH Correct By: 13-Jun-2019

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIR IN THE SKIMMER BOX. Correct By: 11-Jul-2019
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST THE pH Correct By: 13-Jun-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. ADJUST ALKALINITY. Correct By: 13-Jun-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 11-June-2019


Comments
Our records show: The main drain suction outlet cover (Lawson MLD-FGD-1212) was installed date on 5/1/2018. The cover has a 10 year life span and must be replaced before 5-1-28.

-Remember to post a sign at the end of the day and end of the season that states "WARNING: POOL CLOSED"