[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. SUBMIT AN ERN TO ODH FOR THE REPLACEMENT OF THE DISINFECTION UNIT Correct By: 20-Jun-2023
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week. TEST AND RECORD CYA WEEKLY. Correct By: 20-Jun-2023
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The ACC is not connected to the disinfection unit.
All equipment must be maintained in accordance with the manufacturers specifications. THE ACC SHOULD BE DISCONNECTED FROM THE ACID FEEDER IF IT IS NOT CONNECTED TO THE DISINFECTION UNIT. Correct By: 20-Jun-2023
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. One skimmer is missing a weir.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIR IN THE SKIMMER. Correct By: 20-Jun-2023
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE FLOW RATE TO BETWEEN 69 AND 120 GPM
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. INSTALL PRESSURE AND VACUUM GAUGES TO DETERMINE THE FLOW ON THE WATERFALL PUMP.
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times. PLACE A FIRST AID KIT IN THE POOL AREA. Correct By: 20-Jun-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 13-June-2023


Comments
Our records show that the main drain suction outlet covers (AquaStar 8MF) were installed 7-27-2018. The covers have a 5 year life span and must be replaced before 7-27-2023. The waterfall pump outlets covers (AquaStar WAV 12) were installed 7-27-2018. The cover have a 5 year life span and must be replaced before 7-27-2023.

When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm

A bag of DE is on the floor. This should be stored off of the floor to avoid water damage.