[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week. TEST AND RECORD CYANURIC ACID WEEKLY. Correct By: 03-Aug-2020
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. INSTALL THE WEIR IN THE SKIMMER LOCATED BY THE STEPS. Correct By: 31-Aug-2020
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL A BACKFLOW PREVENTER ON THE HOSE BIB IN THE EQUIPMENT ROOM. Correct By: 03-Aug-2020
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Backflow prevention devices were not maintained to function properly
Have the backflow prevention device evaluated or replaced so that backflow is prevented. THE ASSE 1013 BACKFLOW PREVENTER WAS NOT LOCATED AND PRESUMABLY NOT TESTED. LOCATE OR INSTALL THE ASSE 1013 AND HAVE IT INSPECTED ANNUALLY. Correct By: 03-Aug-2020
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE FLOW RATE TO AT LEAST 175 GPM FOR THE POOL. Correct By: 03-Aug-2020
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. DECREASE THE CYANURIC ACID LEVEL. Correct By: 03-Aug-2020


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 29-July-2020


Comments
THE POOL IS 1814 SQ FT. LIFEGUARDS ARE NOT REQUIRED AT THIS SIZE OF POOL. SIGNS THAT MUST BE POSTED ARE "WARNING, NO LIFEGUARD", "SWIMMING ALONE IS NOT RECOMMENDED", AND "CHILDREN MUST BE SUPERVISED". I WILL DOUBLE CHECK WITH ODH, BUT IT IS MY UNDERSTANDING THAT A POOL CANNOT SWITCH BETWEEN A GUARDED POOL AND NON-GUARDED POOL DURING THE DAY TO ACCOMMODATE ADULT SWIMS. OAC 3701-31-04 (E)(4) OAC 3701-31-04 (E)(3)