3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat The free chlorine level is less than required. The required free chlorine level is at least 1 ppm and the level was tested at 0 ppm at the time of inspection.
This violation is a critical operational item and poses an imminent health hazard.
THE POOL MUST CLOSE IMMEDIATELY AND REMAIN CLOSED UNTIL CORRECTED AND THE HEALTH DEPARTMENT VERIFIES COMPLIANCE. Correct By: 13-Dec-2018
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. Correct By: 13-Dec-2018
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The UV light was not functioning.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE UV LIGHT.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present. The hose bib under the eye wash station is not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL A BACKFLOW PREVENTER ON THE HOSE BIB THAT IS LOCATED UNDER THE EYEWASH STATION IN THE PUMP ROOM.
Facility Type: Pool
[?] Inspection Type: Complaint
Inspection Date: 13-December-2018
Comments |
---|
The health department received a notification of several suspected recreational waterborne illnesses associated with this facility. This was discussed with the assistance manager. THE POOL MUST CLOSE IMMEDIATELY AND REMAIN CLOSED UNTIL ALL VIOLATIONS HAVE BEEN CORRECTED AND THE HEALTH DEPARTMENT VERIFIES COMPLIANCE. PLEASE THE HEALTH DEPARTMENT AT 440-322-6367. THE POOL CLOSED AT THE TIME OF INSPECTION AND A" POOL CLOSED" SIGN WAS POSTED. |