3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The drain covers are not VGB compliant covers.
REPLACE THE MAIN DRAIN COVERS WITH COMPLINAT COVERS. RETAIN THE COC, INSTALL INSTRUCTIONS, AND COI.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIRS IN THE SKIMMERS. REPLACEMENTS HAVE REPORTEDLY BEEN ORDERED
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE FILTER DRAIN LINES.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW TO AT LEAST 240 GPM. CHECK THE FLOW METER FIRST FOR FUNCTIONALITY.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-July-2018
Comments |
---|
Corrections that have been made since the last inspection dated 6-6-18 -the ACC flow switch is working -the back flow preventer has bee tested -the flow meter is working, but there is a piece of dirty in it that needs to be cleaned out -the hand rails are tightened -the chlorine tank is labeled, chemicals are not stored on top of each other. THE ACID TANK STILL NEEDS TO BE LABELED -a ring buoy is available. PLACE A 30-60 FT ROPE ON THE RING BUOY -a sign was posted stating the location of the emergency phone |