[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The main drain covers has exceeded their life span.
REPLACE THE MAIN DRAIN COVERS OR PROVIDE DOCUMENTATION AS TO THE DATE OF INSTALLATION OF THE DRAIN COVERS, THE NAME OF THE INSTALLER, AND THE CERTIFICATE OF INSTALLATION. Correct By: 09-Jul-2019
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical There is no disinfectant in the pool. Free chlorine level is 0.
ThIS violation is an imminent health hazard. CLOSE THE POOL IMMEDIATELY AND DO NOT OPEN THE POOL UNTIL THE VIOLATION HAS BEEN CORRECTED AND THE HEALTH DEPARTMENT HAS BEEN CONTACTED. Correct By: 02-Jul-2019
3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The pump was not running while the pool was open.
This violation is an imminent health hazard. CLOSE THE POOL UNTIL THE CIRCULATION IS REPAIRED. Correct By: 01-Jul-2019

3701-31-04 (B)(3) / Staff is trained and knowledgeable
Staff was not trained or knowledgeable in pool operations.
Train staff in pool operations, operation of equipment, chemical storage, use and handling and appropriate emergency procedures. INFORM ALL EMPLOYEES OF THE CRITICAL OPERATING ITEMS. IF THERE IS A CRITICAL OPERATIONAL ITEM THE POOL MUST CLOSE UNTIL IT IS CORRECTED OR REPAIRED. Correct By: 04-Jul-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The weirs are missing in the skimmers
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIRS IN THE SKIMMERS. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bib in the pump room is not backflow protected.
Remove all cross connection hazards from the pool area. INSTALL A ASSE 1011 ON THE HOSE BIB IN THE PUMP ROOM. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The fence has large gaps between the ground and the bottom of the fence. The gate does not self-close and latch.
ELIMINATE GAPS IN THE FENCE OF 4 INCHES OR GREATER BETWEEN THE BOTTOM OF THE FENCE AND GROUND. REPAIR THE GATE SO THAT IT SELF-CLOSES AND LATCHES. Correct By: 09-Jul-2019
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook was not provided at the guarded pool.
Provide the non-telescopic reach pole at the pool at all times. KEEP SHEPHERD'S CROOK ATTACHED TO THE REACH POLE. Correct By: 09-Jul-2019
3701-31-04 (E)(2)(d) / First aid kit provided
Sufficient First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times. PROVIDE MORE BANDAGES FOR THE FIRST AID KIT. Correct By: 09-Jul-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 01-July-2019


Comments
Our records show: The main drain suction outlet cover (AquaStar WAV 12) was installed 5/1/2014. The cover has a 5 year life span and must be replaced before 5/1/2019.