3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
TEST FOR ALKALINITY AT LEAST ONCE A WEEK.
TEST FOR COMBINE CHLORINE DAILY.
USE THE TEST KIT TO TEST THE pH AND COMBINE CHLORINE. Correct By: 29-Oct-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Weir missing in skimmer.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE MISSING WEIR IN SKIMMER.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Corrected During Inspection Equipment was not maintained per manufacturers specifications. Flow rate exceeded the max allowable flow rate of the filter.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE TO BETWEEN 32 AND 48 GPM. FLOW WAS REDUCED AT THE TIME OF INSPECTION BY PARTLY CLOSING THE MAIN VALVE.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY. Correct By: 29-Oct-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 27-October-2021