3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is 0 ppm
This is a critical operational item and poses an imminent health hazard. THE POOL MUST CLOSE UNTIL THE VIOLATION IS CORRECTED (FREE CHLORINE LEVEL IS AT LEAST 1 PPM. Call the health department (440-219-7158) before reopening. Correct By: 26-Jun-2020
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE AUTOMATIC CHEMICAL CONTROLLER Correct By: 26-Jun-2020
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT PLANS TO THE OHIO DEPARTMENT OF HEALTH FOR THE ALTERATION OF THE DECK AND THE FENCE AROUND THE BABY POOL. Correct By: 03-Jul-2020
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING SKIMMER LIDS AND WEIR IN THE SKIMMER Correct By: 03-Jul-2020
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
TRIM THE NAIL THAT IS STICKING OUT OF THE SHEPHERDS CROOK. Correct By: 29-Jun-2020
3701-31-04 (E)(2)(b)(ii) / A back/spine board with straps and head immobilizers
A back/spine board with straps and head immobilizers was not provided at the guarded pool.
Provide a back/spine board with straps and a head immobilizer at the pool at all times.
PLACE THE STRAPS ON THE SPINE BOARD Correct By: 26-Jun-2020
3701-31-04 (E)(4)(e)(vii) / Lifeguards have a CPR pocket mask and rescue tube on their person
Lifeguards did not have a CPR pocket mask and/or rescue tube on their person.
Provide lifeguards with CPR pocket masks and rescue tubes and require that these items be with the lifeguard at all times while on duty.
LIFEGUARDS MUST HAVE A CPR WITH THEM. Correct By: 26-Jun-2020
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 08-July-2020
Comments |
---|
POOL WAS NOT OPEN AT THE TIME OF INSPECTION POST SIGN STATING "WARNING POOL CLOSED" BY THE WADING POOL REMEMBER TO CONTACT ODH ABOUT INSTALLING A FENCE AROUND THE WADING POOL |